The
basic 5204 unit offers local fire alarm control for
up to four zones and central station communications
with the optional UL listed Model 5205 Digital Communicator.
The 5204 provides 3 amp current for external devices
and two 1.5 amp supervised notification circuits. The
system is compatible with both 2- and 4-wire smoke detectors.
The
5204 includes an annunciator inside the cabinet for
annunciation and operation. LEDs are visible without
opening the cabinet. Operation keys include SILENCE,
DIALER RESET, and DISPLAY TROUBLES.
Remote
annunciation is available through the optional Model
5230. This four-wire annunciator can perform the same
operation as the main system annunciator and features
English-language LCD display.
Features
- The
4 Class B (Style B) zones are interchangeable to
Class A (Style D) using the Model 7181 Zone Converter
- Fuseless
design reduces service calls
- Field
selectable 24 or 12 VDC power supply
- 3
amp current output available for external devices
- Compatible
with 2- and 4-wire smoke detectors as well as water
flow and sounding devices
- Two
1.5 amp supervised notification circuits programmable
for steady, pulsing, temporal, supervisory
- Auxiliary
outputs of 1.5 amp at 12 or 24 VDC and 175 mA at
12 VDC (only)
- Smoke
verification, pre-alarm delay and cross-zoning minimize
false alarms
- Two
general purpose relays (2.5A dry contact form C)
- Optional
plug-in UL Listed digital communicator (Model 5205)
- Up/downloading
(reduces service time)
- Programmable
from on-board touchpad or optional remote annunciator
- Accu-Zone
diagnostics
|